Cleanroom Standards – ISO Guidelines

(A) Background:
Before global cleanroom classifications and standards were adopted by the International Standards Organization (ISO), the U.S. General Service Administration’s standards (known as FS209E) were applied virtually worldwide. However, as the need for international standards grew, the ISO established a technical committee and several working groups to delineate its own set of standards.
Difference between FS209E AND ISO 14644-1

                                   FS209E                             ISO 14644-1
FS209E contains six classes. The ISO 14644-1 classification system adds two cleaner standards and one dirtier standard.
The “cleanest” cleanroom in FS209E is referred to as Class 1 AND the “dirtiest” cleanroom is a class 100,000.  The “cleanest” cleanroom is a Class 1 and the “dirtiest” a Class 9.
·       ISO class 3 is approximately equal to FS209E class 1.
·       While ISO class 8 approximately equals FS209E class 100,000.
·       In November 2001, Federal Standard 209E was superseded by the new ISO 14644-1 international standards.
·       References to FS209E are still used.

(B) Airborne Particulate Cleanliness Class Comparison:

    ISO 14644-1              FEDERAL STANDARD 209E
      ISO Class            English         Metric
ISO 1
ISO 2
ISO 3 1 M1.5
ISO 4 10 M2.5
ISO 5 100 M3.5
ISO 6 1,000 M4.5
ISO 7 10,000 M5.5
ISO 8 100,000 M6.5
ISO 9

 
(C) Airborne Particulate Cleanliness Classes (by cubic meter):

CLASS               Number of Particles per Cubic Meter by Micrometer Size
0.1 micron 0.2 micron 0.3 micron 0.5 micron 1 micron 5 microns
ISO1 10 2
ISO2 100 24 10 4
ISO3 1,000 237 102 35 8
ISO4 10,000 2,370 1,020 352 83
ISO5 100,000 23,700 10,200 3,520 832 29
ISO6 1,000,000 237,000 102,000 35,200 8,320 293
ISO7 352,000 83,200 2,930
ISO8 3,520,000 832,000 29,300
ISO9 35,200,000 8,320,000 293,000

Important Points:

  1. In cleanrooms, particulate concentration changes over time — from the construction and installation of equipment to its operational status.
  2. ISO delineates three cleanroom classification standards:
  • as- built
  • at- rest and
  • operational

 
(D) ISO 14644-2: It describes the type and frequency of testing required to conform to certain standards.
The below mentioned tables indicate mandatory and optional tests:

  1. Required Testing (ISO 14644-2)
                                   Schedule of Tests to Demonstrate Continuing Compliance
Test Parameter Class Maximum Time Interval Test Procedure
Particle Count Test <= ISO 5 6 Months ISO 14644-1 Annex A
> ISO 5 12 Months
Air Pressure Difference All Classes 12 Months ISO 14644-1 Annex B5
Airflow All Classes 12 Months ISO 14644-1 Annex B4
  1. Optional Testing (ISO 14644-2)
                                        Schedule of Additional Optional Tests
Test Parameter Class Maximum Time Interval Test Procedure
Installed Filter Leakage All Classes 24 Months ISO 14644-1 Annex B6
Containment Leakage All Classes 24 Months ISO 14644-1 Annex B4
Recovery All Classes 24 Months ISO 14644-1 Annex B13
Airflow Visualization All Classes 24 Months ISO 14644-1 Annex B7
  1. In addition to ISO 14644-1 and ISO 14644-2, eight other cleanroom standards documents exist, as well as three specific to bio-contamination applications.
ISO Document                                              Title
ISO 14644-1 Classification of Air Cleanliness
ISO 14644-2 Cleanroom Testing for Compliance
ISO 14644-3 Methods for Evaluating and Measuring Cleanrooms and Associated Controlled Environments
ISO 14644-4 Cleanroom Design and Construction
ISO 14644-5 Cleanroom Operations
ISO 14644-6 Terms, Definitions and Units
ISO 14644-7 Enhanced Clean Devices
ISO 14644-8 Molecular Contamination
ISO 14644-9 Surface Cleanliness by Particle Concentration
ISO 14644-10 Surface Cleanliness by Chemical Concentration
ISO 14698-1 Bio-Contamination: Control General Principles
ISO 14698-2 Bio-Contamination: Evaluation and Interpretation of Data
ISO 14698-3 Bio-Contamination: Methodology for Measuring Efficiency of Cleaning Inert Surfaces

 (E) ISO and Federal Air Change Rates for Cleanrooms:
What is Air Change Rate (ACR)?
Ans: A critical factor in cleanroom design is controlling air-change per hour (ACH). This refers to the number of times each hour the filtered outside air replaces the existing volume in a building or chamber. A lower ACR often resulted in cleaner air.
Example: – In a normal home, an air-conditioner changes room air 0.5 to 2 times per hour. In a cleanroom, depending on classification and usage, air change occurs anywhere from 10 to more than 600 times an hour.
Use of Air Change Rate (ACR)?
 Ans: ACR is a prime variable in determining ISO and Federal cleanliness standards. To meet optimal standards, ACR must be painstakingly measured and controlled.
Name of the factors due to ACR varies from One Clean- Room to Other?
Ans:  The responsible factors are given below:

  • Internal equipment,
  • Staffing and operational purpose.
  • Everything depends on the level of outside contaminants trying to enter the facility versus the level of contaminants being generated on the inside.

Note: Low-end figures within each contamination class generally indicate air velocity and air change requirements for an as-built or at-rest facility—where no people are present and no contaminating processes under way. When there are people and processes producing contaminants, more air changes are required to maintain optimal cleanliness standards. For instance, some manufacturers insist on as many as 720 air changes per hour to meet Class 10 standards.
Name of the factors required for determining the number of Air Changes for particular application?
Ans: The various factors are mentioned below:

  • The number of personnel,
  • Effectiveness of garbing protocol, frequency of access, and
  • Cleanliness of process equipment.

                       Recommended following ranges based on FS209E classifications

FS Cleanroom Class ISO Equivalent Class Air Change Rate
1 ISO 3 360-540
10 ISO 4 300-540
100 ISO 5 240-480
1,000 ISO 6 150-240
10,000 ISO 7 60-90
100,000 ISO 8 5-48

Describe three abiding principles of ACR?
Ans: The three abiding principles of ACR are:

  • Lower air change rates result in smaller fans, which reduce both initial investment and construction cost.
  • Fan power is proportional to the cube of air change rates or airflow. A 30-percent reduction in air change rate results in a power reduction of approximately 66 percent.
  • By minimizing turbulence, lower airflow may improve cleanliness.

(F) Federal and ISO Ceiling Fan Coverage Specifications:

  • Achieving the optimal air change rate requires proper ceiling fan coverage.
  • The cleanest modular cleanroom incorporates filter/fan units (FFUs) in every 2’ x 4’ (610 mm x 1219 mm) ceiling bay.
  • This near-100% coverage provides a laminar flow of filtered air to quickly remove contaminants from the room, thus meeting FS209E standards for Class 10 and ISO Class 1 standards.
  • Such coverage, especially in a large cleanroom, can lead to higher energy consumption, thus increasing costs for both initial construction and ongoing operation.
  • In most cases, a smaller percentage of ceiling coverage produces adequate cleanliness.
This table illustrates the percentage of ceiling coverage recommended for each cleanliness class, as a range:
                    Class Ceiling Coverage (Percentage)
ISO 8 (Class 100,000) 5 – 15%
ISO 7 (Class 10,000) 15 – 20%
ISO 6 (Class 1,000) 25 – 40%
ISO 5 (Class 100) 35 – 70 %
ISO 4 (Class 10) 50 – 90%
ISO 3 (Class 1) 60 – 100%
ISO 1-2 80 – 100%

Before deciding on the appropriate velocity and air changes for your application, it is recommended to evaluate some factors carefully and name of factors are:

  • Number of personnel,
  • Effectiveness of garbing protocol,
  • Access frequency and
  • Cleanliness of process equipment.

Important Point: Once the required air change figure is established; the number of required FFUs can be determined using this formula:
No. of FFUs = (Air Changes/Hour ÷60) x (Cubic ft. in room÷ 650*)
*CFM output of a loaded FFU
Example: Meeting Class 100 standards using the low-end air change recommendation (240/hour) inside a 12’ x 12’ x 7’ (3302 mm x 3302 mm x 2134 mm) cleanroom, with 1008 cu. ft. of volume, requires 6 FFUs. To meet the same standard using the high-end air change recommendation (480/hour) requires 12 FFUs.
(G) Positive Pressure: Cleanrooms are designed to maintain positive pressure, preventing “unclean” (contaminated) air from flowing inside and less-clean air from flowing into clean areas. The idea is to ensure that filtered air always flows from cleanest to less-clean spaces.
Range of differential air- pressure between spaces: 0.03 to 0.05 inches water gauge is recommended.
Note: In order to minimize disruptions to these cascading pressures when doors are opened, air locks are often specified between rooms of differing ISO cleanliness levels. Automated fan controls simplify pressure balancing by allowing fan speed adjustments at a centralized console panel.                          
(H) Laminar and Turbulent Air Flow:

                        ISO Class 5                          ISO Class 6
ISO 5 (Class 100) and cleaner facilities rely on unidirectional, or laminar, airflow. ISO 6 (Class 1,000) and above cleanrooms generally utilize a non-unidirectional or turbulent airflow.
Laminar airflow means that filtered air is uniformly supplied in one direction (at a fixed velocity) in parallel streams, usually vertically. This means the air is not regulated for direction and speed.
Air is generally re-circulated from the base of the walls back up to the filtering system. The advantage of laminar over turbulent airflow is that it provides a uniform environment and prevents air pockets where contaminants might congregate.

 
For any suggestions & feedback, write to us at: info@pharmastate.com
App Link: https://goo.gl/mS8Lr7
Website: https://www.pharmastate.com
 

One Comment

  • PharmaState Academy
    05/12/2018

    Thank yo for letting us know the standards of clean rooms….

Write a comment